1、 Product Features:
AC voltage acquisition, electrical three terminal isolation, signal conversion, multiple AC voltage inputs are isolated and converted into standard 4-20mA/0-10V analog signals, anti-interference, and protection of PLC/instrument ports;
2、 Core electrical parameters:
1. Input side (AC voltage selectable range, dial setting)
Optional inputs: 0~20VAC/0~24VAC/0~36VAC/0~80VAC/0~120VAC/0~170VAC/0~660VAC
Corresponding input internal resistance: 240k Ω~2500k Ω (automatically matched with range)
Applicable frequency: 15Hz~405Hz;
2. Output side (current type I represents current output)
Standard current output: 0~20mA, 4~20mA optional
Maximum output current: ≤ 22mA
Load capacity: Load resistance<500 Ω
Output ripple: ≤ 50mV;
3. Power Supply (UP=Wide Range Power Supply)
Power supply range: 19.2VAC/DC~253VAC/DC (24~230V AC/DC universal)
Rated power consumption: < 1.1W
Maximum operating current: < 45mA @ 24VDC;
4. Isolation performance (three terminal isolation: input/power/output are isolated from each other)
Rated insulation voltage: 300V AC
Enhanced insulation withstand voltage: Input to power/output 5kVAC withstand voltage test
Overvoltage category: Class III 300V, Class IV 150V;
5. Accuracy and Response
Basic error (15~65Hz power frequency): < ± 1% FS
High frequency error (65~405Hz): < ± 1.3% FS
Temperature drift coefficient:<0.015%/K
Zero/range adjustable range: ± 20%
Step response time (10~90%): < 180ms
Built in lightning protection suppression diode surge protection;
3、 Environmental and mechanical parameters
Working temperature: -25 ℃~+60 ℃
Storage temperature: -40 ℃~+85 ℃ (no condensation)
Maximum operating altitude: ≤ 2000m
Installation: DIN 35mm rail buckle installation, with a minimum spacing of 10mm between multiple units arranged side by side
Wiring: Plug in screw terminal
Protection level: IP20 (inside the shell)
Dimensions: Standard MACX series modular isolation transmitter housing;
4、 Compliance certification
EMC Electromagnetic Compatibility: EN 61000-6-2/EN 61000-6-4
UL, CE certification, IEC 61010 safety standard