Basic Info
Brand: Notifier (Honeywell Fire Safety)
Model: JSM-FMM-1C (FMM-1)
Product Type: Addressable Single Monitor Input Module
Compatible Panel: NFS2-640, NFS2-3030 ONYX series fire alarm control panels
Function: Monitors dry contact signals of fire equipment (water flow switch, fire hydrant button, pressure switch, valve feedback, etc.)
Electrical Parameters
Operating Voltage: 15 ~ 32 VDC SLC bus-powered, no separate external 24V supply
Standby Current: 270 μA (LED green flashing during normal polling)
Alarm Max Current: 5.1 mA (red LED steady on under alarm state)
End-of-Line Resistor (EOL): 3.9 kΩ (required for circuit supervision)
Max loop wiring resistance: 25 Ω
Address Setting: Two-digit decimal dial switch, address range 0~159, occupies 1 single SLC loop address
Mechanical & Environmental
Terminal Type: SEMS screw terminals, convenient wiring & maintenance
Indicator: Bi-color dual LED; Green flash = normal patrol, Red steady = alarm trigger
Operating Temp: -10℃ ~ +60℃
Relative Humidity: 10% ~ 93% RH, non-condensing
Overall Dimension: 114.3(H) × 101.6(W) × 31.75(D) mm
Installation: Surface wall mounting, separate back box required