1. Main power circuit
– Rated insulation voltage Ui: 690 V AC
– Impulse withstand voltage Uimp: 6 kV
– Applicable frequency: 0–400 Hz
– Max matched motor power: 5.5 kW @ 400 V AC
2. Aux signal contacts
– Thermal rated current Ith: 5 A
– AC-15 rating: 3 A / 120 V AC
– DC-13 rating: 0.22 A / 125 V DC
3. Trip threshold: 1.14 ± 0.06 × set current