Item Technical Data
Auxiliary Power Supply Universal 24–240 V AC / 24–240 V DC (wide range)
Supply Tolerance AC: 85–110% Un; DC:70–120% Un
Power Consumption (Quiescent) <5.0 VA
Rated Frequency 50 Hz / 60 Hz auto-adaptive
CT Secondary Rated Current Site-selectable 1 A or 5 A
Thermal Withstand (CT Input) Continuous: 4 A (1A CT) / 20 A (5A CT); 1s withstand: 100 A / 500 A
Binary Inputs 4 configurable digital inputs (24–240 V wide voltage compatible)
Binary Outputs 6 outputs total: 2 power trip outputs + 4 signal alarm outputs
Protection Class IP54 front panel; IP20 rear terminal area
Operating Ambient Temp -20 °C ~ +55 °C
Storage Temperature -40 °C ~ +70 °C