Series: Centum‑VP FIO
Module Type: Digital Input DI Module
Channel: 32‑channel, group‑isolated (16 ch per group common‑side)
Rated Input Voltage: 24 V DC, sink / source compatible
Input ON threshold: 18‑26.4 V DC
Input OFF threshold: ≤5.0 V DC
Per‑channel input current: 4.1 mA ±20%
Max allowable input voltage: 30 V DC