1. Model: MTL5561
2. Brand: Eaton MTL
3. Channel: 2-channel, loop powered type
4. Power supply voltage: 6-30 V DC
5. Signal current range: 1-40 mA (conventional smoke/temperature sensing circuit)
6. Intrinsic safety parameters (single channel): Uo=28V, Io=93mA, Po=0.65W; Um=253V AC/DC
7. Response time: Step input, stable to within 5% of the final value within 1.5ms
8. Accuracy: The transmission accuracy is better than 400 µ A at 20 ℃
9. Temperature drift: 0-60 ℃ < 4 µ A/℃; -20~0℃ <15µA/℃
101. Single channel power consumption: maximum 0.7W at 24V/40mA signal; maximum 0.9W at 30V/40mA signal
11. Protection: IP54
12. Installation: 35mm DIN rail buckle installation
13. Working temperature: -20 ℃~+60 ℃
14. Explosion proof certification: ATEX, IECEx, CCC; Support Zone 0, IIC T4~T6, Div.1 Group A hazardous areas
15. Functional features: Input reverse polarity protection, fault free ground fault detection, electrical isolation
16. SIL: Single SIL2; Redundant configuration can reach SIL3