1. Model: MTL5561
2. Brand: Eaton MTL
3. Channel: 2-channel, loop powered type
4. Power supply voltage: 6-30 V DC
5. Signal current range: 1-40 mA (conventional smoke/temperature sensing circuit)
6. Intrinsic safety parameters (single channel): Uo=28V, Io=93mA, Po=0.65W; Um=253V AC/DC
7. Response time: Step input, stable to within 5% of the final value within 1.5ms
8. Accuracy: The transmission accuracy is better than 400 µ A at 20 ℃
9. Temperature drift: 0-60 ℃ < 4 µ A/℃; -20~0℃ <15µA/℃
101. Single channel power consumption: maximum 0.7W at 24V/40mA signal; maximum 0.9W at 30V/40mA signal
11. Protection: IP54
12. Installation: 35mm DIN rail buckle installation
13. Working temperature: -20 ℃~+60 ℃
14. Explosion proof certification: ATEX, IECEx, CCC; Support Zone 0, IIC T4~T6, Div.1 Group A hazardous areas
15. Functional features: Input reverse polarity protection, fault free ground fault detection, electrical isolation
16. SIL: Single SIL2; Redundant configuration can reach SIL3
2-channel intrinsic safety fire smoke detector interface,MTL5561 Specifications
| 1. Model | MTL5561 |
|---|---|
| 2. Brand | Eaton MTL |
| 3. Channel | 2-channel, loop powered type |
| 4. Power supply voltage | 6-30 V DC |
| 5. Signal current range | 1-40 mA (conventional smoke/temperature sensing circuit) |
| 7. Response time | Step input, stable to within 5% of the final value within 1.5ms |
| 8. Accuracy | The transmission accuracy is better than 400 µ A at 20 ℃ |
| 9. Temperature drift | 0-60 ℃ < 4 µ A/℃; -20~0℃ <15µA/℃ |
| 101. Single channel power consumption | maximum 0.7W at 24V/40mA signal; maximum 0.9W at 30V/40mA signal |
| 11. Protection | IP54 |
| 12. Installation | 35mm DIN rail buckle installation |
| 13. Working temperature | -20 ℃~+60 ℃ |
| 14. Explosion proof certification | ATEX, IECEx, CCC; Support Zone 0, IIC T4~T6, Div.1 Group A hazardous areas |
| 15. Functional features | Input reverse polarity protection, fault free ground fault detection, electrical isolation |
| 16. SIL | Single SIL2; Redundant configuration can reach SIL3 |
About the 2-channel intrinsic safety fire smoke detector interface,MTL5561
The 2-channel intrinsic safety fire smoke detector interface,MTL5561 is a electrical products used in industrial automation, control and power systems. It is rated at 1. Model MTL5561, 2. Brand Eaton MTL, 3. Channel 2-channel, loop powered type. This electrical products is supplied as new, original industrial-grade stock. Each unit is identified by manufacturer part number 2-channel intrinsic safety fire smoke detector interface,MTL5561 for accurate procurement and cross-referencing.
Why source the 2-channel intrinsic safety fire smoke detector interface,MTL5561 from HDE123
- Verified part number: every 2-channel intrinsic safety fire smoke detector interface,MTL5561 is checked against its manufacturer specification before shipment.
- 15 confirmed technical parameters available on this page for engineering review.
- Global delivery with clear lead time and commercial invoice for B2B buyers.
- Fast B2B support: send us the equipment model or an existing part number and our engineers confirm compatibility before you order.
Ordering the 2-channel intrinsic safety fire smoke detector interface,MTL5561
To order the 2-channel intrinsic safety fire smoke detector interface,MTL5561, add it to your cart and complete checkout, or use the Request a Quote form for volume purchases and replacement / cross-reference enquiries. Lead time: typically 3–10 working days for in-stock items, subject to confirmation. Worldwide shipping is available and a commercial invoice is provided for customs.