Model attribute: PM240-2 unfiltered power module, integrated built-in braking chopper, no onboard EMC input filterretekltd.c…
Input power supply: 3-phase AC 380V~480V, tolerance ±10%, frequency 47~63Hz
Rated power & output current (dual load rating)
High Overload HO (heavy constant torque load): 2.2 kW, 5.9A continuous output current, operating temperature -10℃ ~ +50℃
Overload capability: 200% for 3s, 150% for 57s within 300s cycle
Low Overload LO (fan/pump quadratic torque load): 3.0 kW, 7.7A continuous output current, operating temperature -10℃ ~ +40℃ (derate above 40℃)
Overload capability: 150% for 3s, 110% for 57s within 300s cycle