Rated Current (In): 16 A
Rated Voltage (Un): AC 230/400 V
Rated Frequency: 50/60 Hz
Short-time Withstand Current: 1.25×In (for 1 hour, no tripping)
Tripping Characteristics:
– Instantaneous tripping current: 5×In ~ 10×In (3×In no tripping)
– Tripping time at 1.13×In: ≤ 1 hour
– Tripping time at 1.45×In: ≥ 1 hour (no tripping)
Operating Temperature: -25℃ ~ +70℃ (derating required above 60℃)
Storage Temperature: -40℃ ~ +85℃
Pollution Degree: 2
Altitude: ≤ 2000 m (derating 1% per 100 m above 2000 m)
Protection Class: IP20