1、 Power supply parameters
Working voltage: AC/DC 85-265V (universal for both AC and DC, compatible with AC220V/DC220V/DC110V)
Static power consumption of the whole machine: ≤ 22mA
Power circuit withstand voltage: The shell and power terminal are AC2000V/1min without breakdown
2、 Switch input (6-way passive dry contact, model suffix 6 meaning)
Collect 6 sets of passive auxiliary contacts for primary equipment of high-voltage cabinets, without external power supply:
Circuit breaker opening and closing positions
Hand cart testing position, working position
Grounding switch opening and closing
Spring energy storage status
Input characteristics: Passive contact, conducting impedance10M Ω, no power supply to equipment inside the cabinet.
3、 High voltage live display circuit
Compatible with high-voltage sensors, with a sensing threshold of 100V to 150V
A/B/C three-phase independent LED indicator lights, automatic alarm for phase loss
Live forced locking output: relay passive contact AC220V/5A
4、 Temperature and humidity measurement and control (standard dual heating output)
Temperature measurement range: -20 ℃ to 70 ℃; Humidity measurement: 0-99% RH
Heating output: 2-channel relay contacts, maximum load per channel 500W
Working mode: automatic/manual heating switch, heating disconnection fault alarm
Condensation start-up threshold: humidity>85% RH, automatic start heater
5、 Capacity of operation and output contacts
Local opening and closing knob: built-in control circuit, output contact AC220V/10A
Alarm output (temperature and humidity fault, live alarm): Passive normally open AC220V/5A
Voice prompt module: anti misoperation voice broadcast, built-in speaker
6、 Communication (optional)
RS485 Modbus-RTU, Collect all status, temperature and humidity and upload them to the backend; Bus isolation withstand voltage 1000V.
7、 Mechanical installation dimensions
Panel appearance: 192mm (width) × 72mm (height)
Cabinet opening: 186mm × 66mm
Installation depth: Embedded in cabinet ≥ 80mm, snap on installation
Panel protection level: IP30
8、 Environmental adaptation parameters
Working temperature: -20 ℃~+70 ℃
Storage temperature: -40 ℃ to+85 ℃
Relative humidity: ≤ 95% RH, no condensation or freezing
Anti interference: Complies with IEC61000 Level 4 electrical fast pulse group and electrostatic discharge protection
9、 Insulation and Safety
Input/output insulation resistance to ground ≥ 100M Ω
All terminals have a withstand voltage of AC2000V/1min against the metal casing
The whole machine has a flame-retardant shell that is compatible with KYN28, HXGN, and XGN high-voltage switchgear